Sign In | Join Free | My xpshou.com |
|
Brand Name : VENTECH
Model Number : Fan coil unit
Certification : CE
Place of Origin : CHINA
MOQ : 1 unit
Price : 1000USD-5000USD/unit
Payment Terms : L/C, T/T, Western Union
Supply Ability : 50 Containers Per Month
Delivery Time : 30-60days
Packaging Details : standard pallet packing
Product name : Fan coil unit
Model : Fan coil unit
Standard : International standard
Length : MAX:50ft
Feature : Adjustable
Cooling capacity : 21.5~576.7kw
Heating capacity : 22.6~596.4kw
Trade mark : VENTECH
Model | FP200KM4 | FP300KM4 | FP400KM4 | FP500KM4 | FP600KM4 | FP800KM4 | FP1000 KM4-Q |
FP1200KM4 | FP1400KM4 | |||
Air volume | Q | H | m3/h | 360 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
M | 250 | 420 | 560 | 650 | 780 | 1050 | 1310 | 1570 | 1830 | |||
L | 200 | 350 | 460 | 520 | 600 | 800 | 1010 | 1210 | 1410 | |||
Z | H | m3/h | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
M | 280 | 390 | 520 | 650 | 785 | 1030 | 1380 | 1530 | 1980 | |||
L | 230 | 300 | 400 | 500 | 605 | 860 | 1060 | 1170 | 1650 | |||
Cooling capacity | Q | H | W | 2000 | 2710 | 3620 | 4530 | 5440 | 7200 | 9100 | 10500 | 12500 |
M | 1700 | 2410 | 3100 | 3830 | 4485 | 6000 | 7050 | 8560 | 10500 | |||
L | 1500 | 2140 | 2750 | 3360 | 3500 | 4500 | 5500 | 6710 | 8450 | |||
Z | H | W | 1750 | 2620 | 3500 | 4370 | 5400 | 7000 | 8750 | 10500 | 12150 | |
M | 1410 | 2250 | 2920 | 3645 | 4440 | 5890 | 7340 | 8800 | 10130 | |||
L | 1020 | 1860 | 2430 | 3040 | 3745 | 4900 | 6110 | 7260 | 8450 | |||
Heating capacity | Q | H | W | 3000 | 4070 | 5440 | 6800 | 8160 | 10800 | 13700 | 16000 | 18600 |
M | 2810 | 3520 | 4650 | 5750 | 6700 | 9350 | 10600 | 13700 | 15260 | |||
L | 2480 | 3150 | 4130 | 5100 | 5200 | 7690 | 8300 | 11200 | 12700 | |||
Z | H | W | 2770 | 4130 | 5250 | 6750 | 8100 | 10500 | 13120 | 15730 | 17500 | |
M | 1990 | 3010 | 4370 | 5460 | 6450 | 8750 | 10940 | 12530 | 14580 | |||
L | 1310 | 2530 | 3645 | 4370 | 5190 | 7290 | 8990 | 10920 | 12150 | |||
Noise level | Q | ≤dB(A) | ≤dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
Z | ≤dB(A) | ≤dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 50 | 52 | |
Power source | V/Ph/Hz | V/Ph/Hz | 220-240V/1/50Hz | |||||||||
Motor | Q | Input | W | 46 | 52 | 70 | 80 | 93 | 130 | 150 | 231 | 268 |
Z | Input | W | $32 | 36 | 36 | 60 | 66 | 90 | 124 | 180 | 225 | |
Heat exchanger | Type | Copper pipe with aluminum fins | ||||||||||
Q cooling |
Water flow | m3/h | 0.31 | 0.48 | 0.65 | 0.81 | 0.98 | 1.28 | 1.65 | 1.99 | 2.26 | |
WPD | kPa | 10 | 18 | 22 | 28 | 37 | 35 | 30 | 35 | 50 | ||
Q heating |
Water flow | m3/h | 0.31 | 0.48 | 0.65 | 0.81 | 0.98 | 1.28 | 1.65 | 1.99 | 2.26 | |
WPD | kPa | 10 | 18 | 22 | 28 | 37 | 35 | 30 | 35 | 50 | ||
Z cooling |
Water flow | m3/h | 0.3 | 0.46 | 0.63 | 0.79 | 0.96 | 1 26 | 1.63 | 1.97 | 2.24 | |
WPD | kPa | 30 | 30 | 30 | 30 | 40 | 40 | 40 | 40 | 50 | ||
Z heating |
Water flow | m3/h | 0.3 | 0. 46 | 0.63 | 0.79 | 0.96 | 1.26 | 1.63 | 1.97 | 2. 24 | |
WPD | kPa | 30 | 30 | 30 | 30 | 40 | 40 | 40 | 40 | 50 | ||
Max working pressure | MPa | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | ||
Dimension | Q | Length | mm | 650 | 650 | 650 | 850 | 850 | 850 | 1050 | 1050 | 1050 |
Z | mm | 620 | 620 | 790 | 790 | 1040 | 1140 | 1140 | 1140 | 1140 | ||
Q | Width | mm | 650 | 650 | 650 | 850 | 850 | 850 | 1050 | 1050 | 1050 | |
Z | mm | 620 | 620 | 790 | 790 | 790 | 790 | 990 | 990 | 990 | ||
Q | Height | mm | 278 | 278 | 318 | 318 | 318 | 318 | 318 | 318 | 318 | |
Z | mm | 430 | 430 | 430 | 430 | 430 | 430 | 430 | 430 | 430 | ||
Unit net weight | Q | kg | 26 | 26 | 28 | 34 | 34 | 36 | 50 | 50 | 50 | |
Z | kg | 27 | 27 | 32 | 32 | 37 | 39 | 49 | 49 | 49 |
A floor standing air conditioner is another type of split air conditioner with the difference that the indoor unit is kept on the floor. The other aspects remain the same. There is a refrigerant pipe that connects to a condenser unit outside the premises.
The floor-standing AC is typically available in higher capacities than split ductless wall mounted aircons. The standing ACs are ideal for large halls that the glass windows. The glass allows heat to be trapped inside the premises.
Since the source of heat is located at one corner of the hall, floor standing air conditioners do a better job of maintaining a uniform temperature inside. They trap the heat at the source and vent it off to the atmosphere.
Floor standing units are expensive because they typically have a capacity higher than 3 tons. Multiple fans add to the cost. However, considering the benefits of a floor standing AC, the pros outweigh the cons.
❤ Want to learn more about Vcare Wholehouse air conditioner,please contact us by email directly.
Email:karen@chinaventech.com
Tel:0086 13620119598
![]() |